Selecting the proper valve body requires the following data:
Fluid type
Fluid temperature
Port size (Cv rating)
Selecting the proper port size requires the following data:
Inlet pressure
Required flow rate in either GPM (liquid) or lbs/hr (steam).
If the customer is using on-off control, just select the valve body with the largest port size in the requested pipe size. Remember the following rule when sizing the valve for proportional control. “At least one-half of the available pressure must drop across the valve body when the valve is fully open.” An oversized valve body will result in very nonlinear control action. It is better to have too small of a valve body than too large of one. Please refer to the section on valve sizing (beginning on 5- 37) for complete data.